FREE SHIPPINGFree shipping on all orders over 100000 INR.

Oxygen Treat Scavanger PWD 25 Kg

0
No votes yet

Product Qty Per Unit: 
25.00
Product usage unit: 
Kg.PWD

Negotiate Price

Product Delivery Locations: 
Mumbai, JNPT, Nhava Seva, Pirpav Jetty, Ballard Pier, Mumbai Port Trust, Butcher Island, ONGC EMR Shed, MIdc, Pune, Maharastra
Category: 
Boiler Chemicals-42
Generic Name: 
Oxygen Scavenger Powder
This is most common oxygen scavengers used to effectively remove dissolved OXYGEN from your feedwater. Other grades of 5006 has its own advantages depending on your system and personal preferences
Product Description: 

This is most common Oxygen Treatment Scavanger  used to effectively remove dissolved  OXYGEN from your feedwater. Other grades of 5006  has its own advantages depending on your system and personal preferences ) By the presence of dissolved oxygen in water system , corrosion and pitting caused on metal surface. RXSOL 5006 is a specially formulated and  powdered materials.  which, when added to boiler feedwater, removes dissolved oxygen , By acting as an Oxygen Treatment Scavanger.

Benefits:- By Control of corrosive oxygen from boiler water which causes corrosion and pitting ,It  improves boiler system long life and  reliability .

In boiler feedwater conditioning RXSOL-40-5023-210 is fed to a boiler to remove dissolved oxygen and thus prevent pitting. For the reaction between RXSOL-40-5023-210 and oxygen to proceed rapidly and completely, it is necessary to maintain an excess sulfite concentration at an elevated temperature. 

Product Application: 

The use of RXSOL-40-5023-210 as a chemical deoxygenator is economical within certain limitations imposed by the dissolved oxygen content of the feedwater. If appreciable quantities of dissolved oxygen are permitted to enter the boiler, costs will be high if RXSOL-40-5023-210 is relied on as the sole means of oxygen removal. Generally, costs are balanced by removal of as much of the oxygen as feasible by mechanical means, e.g. deaerator and by using RXSOL-40-5023-210 to react with the residual oxygen.

To prevent corrosion and pitting in feed lines, closed heaters and economizers, it is desirable to feed the RXSOL-40-5023-210 continuously to the boiler feedwater rather than directly to the boiler feedwater rather than directly to the boiler. Reaction between RXSOL-40-5023-210 and oxygen is not instantaneous and the completion of the reaction is aided by the longer contact times provided by feeding RXSOL-40-5023-210 to the feedwater.

 

Catalyzed RXSOL-40-5023-210 will, however, react almost instantaneously with dissolved oxygen even at cold water temperatures. Because of this property, catalyzed RXSOL-40-5023-210 has found increased use in the treatment of cooling water, process water, distribution system, etc. for preventing oxygen corrosion.  

Product Procedure: 
Product Note: 
Product Technical Specification: 

BENEFITS -

RAPID REACTION :

The catalyst RXSOL-40-5023-210 speeds up the removal of dissolved oxygen. Oxygen can be removed completely even from cold water due to catalytic action. Normal reaction time is as low as 15 to 20 seconds as against 10 to 30 minutes for uncatalysed sulphite.

EASY TO HANDLE :

RXSOL-40-5023-210 is a free flowing powder. It is soluble in water even at lower feed water temperature.It is non-toxic and non-corrosive and, therefore, can be handled easily.

pH CONTROL :

RXSOL-40-5023-210 is formulated to get proper pH control for optimum availability of catalyst for rapid oxygen removal.

COST EFFECTIVE :

The catalytic action reduces the excessive requirement of sulphite in feed water for the rapid removal of oxygen. Thus the quantity required is lower, making RXSOL-40-5023-210 treatment cost effective.

APPLICATION AND DOSAGE :

RXSOL-40-5023-210 solution should be dosed continuously. Dissolve the required quantity of RXSOL-40-5023-210 gently in boiler feed water in a separate tank. Dose this solution continuously in the boiler feed water line after the deaerator.

Above 8 ppm of sodium sulphite is required for the removal of 1 ppm of dissolved oxygen from boiler
feed water. About 10% to 20% of excess sulphite should be dosed to provide oxygen consuming reserve.

The table below gives the approximate dosage.

Feed Water Temperature RXSOL-40-5023-210 dosage in gms per ton ofsteam generation

More than 80oC
15
60 to 80oC 30
40 to 60oC 60
Less than 40oC 100

The rmax will provide technical assistance in arriving at optimum dosages for your operating conditions and requirements and in selecting a suitable dosing system for your plant

Product pack size: 
5, 10, 25, 50 Kg JAR
Product alias: 
<p> Maxtreat 3222, Oxygen Treat Scavanger PWD 25 Kg powder</p>

Oxygen Scavanger manufacturer, supplier and exporter. We are keeping ready stock of Oxygen Scavanger at Gandhidham ( Kandla, Sikka, Mundra ), Mumbai ( JNPT, Pirpav, chembur ), Visakhapatnam ( Gangavaram ), Kolkata ( Haldia, Buzbuz, Paradip ), chennai - Ennore. And Largest stockist and supplier of Oxygen Scavanger in Gulf - fujairah, sharjah, Dubai, Abudhabi, Muscat Oman, Barka, Nairobi Kenya Africa.

Remarks: 

Oxygen Treatment Scavanger

  • MUMBAI PORT NHAVA SEVASupply can be done within 1 Hour for BPT-Nhava.
  • Mumbai JNPT Ship Chandler50% Discount on every Marine chemical purchase.
  • Largest Marine CHEM SupplierStock Turbha, KANDLA, Vizag, Kolkata, Chennai.
  • Email Price, MSDS, Tech supportmarinechemical @ gmail.com

Top Rated Products